| Plan Review Notes For Permit 17080671 |
| Permit Number |
17080671 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-27 18:30:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FROM FIRST REVIEW: | | | | | | 1. FBC A 404.2.4, SEE ALSO FIGURE 404.2.4.1(A), 18" | | | MANEUVERING CLEARANCE REQUIRED FOR DOOR 1. SEE ALSO FBC | | | A 203.9 REGARDING EMPLOYEE WORK AREAS. IF ARCHITECT | | | FEELS THAT THIS DOOR IS EXEMPT, PLEASE SEND RATIONALE | | | VIA EMAIL PRIOR TO RESUBMITTING. PLAN WILL BE REQUIRED | | | TO BE REVISED TO INCLUDE RATIONALE IF THE 18" | | | MANEUVERING CLEARANCE IS NOT PROVIDED. | | | | | | 2ND REVIEW, ARCHITECT'S RESPONSE (A LETTER WHICH IS NOT | | | SIGNED AND SEALED AND IS NOT A PART OF THE PERMIT | | | DOCUMENTS) IS THAT THIS IS A CONVENIENCE DOOR AND | | | DISABLED EMPLOYEES CAN USE ANOTHER ROUTE. PLEASE SEE | | | FIRST REVIEW WHICH REQUESTED THAT THIS RATIONALE SENT | | | VIA EMAIL FOR PRELIMINARY REVIEW AND TO BE PUT ON THE | | | PLAN. | | | | | | PLEASE SEE FBC A 206.2.8 AND 402. BASED ON ARCHITECT'S | | | RESPONSE, IT APPEARS THAT THIS DOOR NEEDS TO COMPLY | | | WITH THE REQUIREMENTS OF 404. IF ARCHITECT WOULD LIKE | | | TO CLAIM ONE OF THE EXCEPTIONS IN 206.2.8, PLEASE SEND | | | RATIONAL VIA EMAIL TO AVOID A 3RD REVIEW SUBMITTAL. | | | |
|