Plan Review Notes
Plan Review Notes For Permit 17080671
Permit Number 17080671
Review Stop B
Sequence Number 2
Notes
Date Text
2017-11-27 18:30:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM FIRST REVIEW:
  
 1. FBC A 404.2.4, SEE ALSO FIGURE 404.2.4.1(A), 18"
 MANEUVERING CLEARANCE REQUIRED FOR DOOR 1. SEE ALSO FBC
 A 203.9 REGARDING EMPLOYEE WORK AREAS. IF ARCHITECT
 FEELS THAT THIS DOOR IS EXEMPT, PLEASE SEND RATIONALE
 VIA EMAIL PRIOR TO RESUBMITTING. PLAN WILL BE REQUIRED
 TO BE REVISED TO INCLUDE RATIONALE IF THE 18"
 MANEUVERING CLEARANCE IS NOT PROVIDED.
  
 2ND REVIEW, ARCHITECT'S RESPONSE (A LETTER WHICH IS NOT
 SIGNED AND SEALED AND IS NOT A PART OF THE PERMIT
 DOCUMENTS) IS THAT THIS IS A CONVENIENCE DOOR AND
 DISABLED EMPLOYEES CAN USE ANOTHER ROUTE. PLEASE SEE
 FIRST REVIEW WHICH REQUESTED THAT THIS RATIONALE SENT
 VIA EMAIL FOR PRELIMINARY REVIEW AND TO BE PUT ON THE
 PLAN.
  
 PLEASE SEE FBC A 206.2.8 AND 402. BASED ON ARCHITECT'S
 RESPONSE, IT APPEARS THAT THIS DOOR NEEDS TO COMPLY
 WITH THE REQUIREMENTS OF 404. IF ARCHITECT WOULD LIKE
 TO CLAIM ONE OF THE EXCEPTIONS IN 206.2.8, PLEASE SEND
 RATIONAL VIA EMAIL TO AVOID A 3RD REVIEW SUBMITTAL.
  