| Plan Review Notes For Permit 17080665 |
| Permit Number |
17080665 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-06 11:04:55 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080665 | | | 9/6/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE VERIFICATION THE COOLING TOWER IS LISTED IN | | | ACCORDANCE WITH UL 1995- SECTION 908.1. | | | | | | 2) THE LETTER FROM P.E. JAMES A. MARX JR CERTIFYING THE | | | COOLING TOWER STRUCTURE AND ANCHORAGE DESIGN PER THE | | | WIND STRUCTURAL ANALYSIS REPORT IS REQUIRED TO BE | | | ELECTRONICALLY SIGNED AND SEALED- SECTION 61G15-23.005 | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|