2017-09-06 11:04:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080665
 9/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE VERIFICATION THE COOLING TOWER IS LISTED IN
 ACCORDANCE WITH UL 1995- SECTION 908.1.
  
 2) THE LETTER FROM P.E. JAMES A. MARX JR CERTIFYING THE
 COOLING TOWER STRUCTURE AND ANCHORAGE DESIGN PER THE
 WIND STRUCTURAL ANALYSIS REPORT IS REQUIRED TO BE
 ELECTRONICALLY SIGNED AND SEALED- SECTION 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER