| Plan Review Notes For Permit 17080653 |
| Permit Number |
17080653 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-25 12:59:04 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT # 17080653 | | | 8/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM OF THE NEW 5.0-TON RTU- SECTION 606.2.1. AN | | | EXCEPTION TO THE REQUIREMENT CAN BE MADE IF | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM DOES | | | NOT HAVE THE CAPACITY TO EXCEED 2000 CFMS OF SUPPLY | | | AIR. PLEASE NOTE THAT THE AC SYSTEM INDICATES 1950 | | | CFRMS OF SUPPLY AIR HOWEVER THE PLAN INDICATES ONLY | | | 1350 CFMS OF AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|