2017-08-25 12:59:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT # 17080653
 8/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE NEW 5.0-TON RTU- SECTION 606.2.1. AN
 EXCEPTION TO THE REQUIREMENT CAN BE MADE IF
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM DOES
 NOT HAVE THE CAPACITY TO EXCEED 2000 CFMS OF SUPPLY
 AIR. PLEASE NOTE THAT THE AC SYSTEM INDICATES 1950
 CFRMS OF SUPPLY AIR HOWEVER THE PLAN INDICATES ONLY
 1350 CFMS OF AIR.
  