| Plan Review Notes For Permit 17080651 |
| Permit Number |
17080651 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-31 16:29:44 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080651 | | | BRISTOL MECH SUBMITTALS | | | 8/31/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE UNIDENTIFIED PLAN SHEET THAT HAS BEEN "ATTACHED | | | FOR REFERENCE" IN THE SUBMITTAL SHOWS ALTERATIONS TO | | | THE FIRE/SMOKE AND FIRE DAMPER LOCATIONS. PLEASE | | | INDICATE WHICH PLAN SHEETS, AND WHICH FLOORS OF THE | | | BUILDING ARE AFFECTED BY THESE CHANGES BY SUBMITTING A | | | NARRATIVE. CLARIFY IF THESE CHANGES ARE PART OF A | | | REVISION THAT IS CURRENTLY IN FOR REVIEW, OR WILL BE IN | | | FOR REVIEW AT A | | | | | | LATER DATE. PLEASE NOTE THAT ALL CHANGES TO THE | | | APPROVED SMOKE CONTROL DESIGN MUST BE APPROVED BY THE | | | DESIGN PROFESSIONALS OF RECORD, AND SLS WHO PREPARED | | | THE SMOKE CONTROL RATIONAL ANALYSIS REPORT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|