| Notes |
| Date |
Text |
| 2017-08-21 17:32:04 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080643 | | | 8/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE FLEX DUCT SIZES SHOWN ON THE PLANS APPEAR TO BE | | | OVERSIZED FOR THE AMOUNT OF AIR BEING SUPPLIED. PLEASE | | | VERIFY THAT THESE SIZES- 18" FOR 345 CFMS, 12" FOR 140 | | | CFMS ETC. ARE CORRECT. | | | | | | 2) PROVIDE A DAMPER FOR THE OUTSIDE AIR INTAKE DUCT | | | THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEM OR SPACE | | | IS NOT IN USE- SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|