2017-08-16 11:08:54CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SHOW WINDOW OUTLET PER CODE. NEC 210.62
 2. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING PER FBC ENERGY CODE. FBC C405.2.4
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC C405.7.1
 4. PLAN SHOWS CIRCUIT A-26 AS THE SIGN CIRCUIT, BUT THE
 PANEL SCHEDULE SHOWS CIRCUIT A-13 AS THE SIGN CIRCUIT.
 CLARIFY AND/OR CORRECT. FBC 107.2.1
 5. PANEL SCHEDULE SHOWS CIRCUIT A-5 FEEDING "DIM HH
 THERAPY LIGHTING". I DO NOT SEE THIS CIRCUIT OR THE
 LIGHTING ON THE PLAN. CLARIFY AND/OR CORRECT. FBC
 107.2.1
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW ANY
 AUTOMATIC CONTROL. FBC C405.2.2, 405.2.2.2
 7. PROVIDE INTERIOR LIGHTING CALCULATION, INCLUDING NEW
 FIXTURES ADDED, SHOWING COMPLIANCE WITH THE FBC ENERGY
 CODE FOR THE SPACE. FBC C405.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  