| 2017-08-16 11:08:54 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE SHOW WINDOW OUTLET PER CODE. NEC 210.62 |
| | 2. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW |
| | LIGHTING PER FBC ENERGY CODE. FBC C405.2.4 |
| | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. FBC C405.7.1 |
| | 4. PLAN SHOWS CIRCUIT A-26 AS THE SIGN CIRCUIT, BUT THE |
| | PANEL SCHEDULE SHOWS CIRCUIT A-13 AS THE SIGN CIRCUIT. |
| | CLARIFY AND/OR CORRECT. FBC 107.2.1 |
| | 5. PANEL SCHEDULE SHOWS CIRCUIT A-5 FEEDING "DIM HH |
| | THERAPY LIGHTING". I DO NOT SEE THIS CIRCUIT OR THE |
| | LIGHTING ON THE PLAN. CLARIFY AND/OR CORRECT. FBC |
| | 107.2.1 |
| | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW ANY |
| | AUTOMATIC CONTROL. FBC C405.2.2, 405.2.2.2 |
| | 7. PROVIDE INTERIOR LIGHTING CALCULATION, INCLUDING NEW |
| | FIXTURES ADDED, SHOWING COMPLIANCE WITH THE FBC ENERGY |
| | CODE FOR THE SPACE. FBC C405.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |