| 2017-11-14 12:17:23 | RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM |
| | WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM WINDOWS |
| | TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC. |
| | 704 OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. SIZES OF WINDOWS SHOWN ON THE |
| | FLOOR PLAN ON SHEET A-2 DON'T MATCH SIZES SHOWN ON THE |
| | EXTERIOR ELEVATIONS ON SHEET A-3. REVISE AS REQUIRED TO |
| | MATCH. MASTER BEDROOM AND BEDROOM #2 WINDOW SIZE SHOWN |
| | ON PLAN DON'T MATCH THOSE SHOWN ON THE ELEVATIONS. |
| | NOTE: THE ONLY WINDOW SIZES THAT COMPLY WITH ALL THE |
| | EGRESS REQUIREMENTS ARE THE 36" X 63" SINGLE HUNG |
| | WINDOW SPECIFIED FOR BEDROOM #2 ON THE EAST ELEVATION |
| | AND THE 36" X 72" SINGLE HUNG WINDOWS SPECIFIED FOR THE |
| | MASTER BEDROOM. THE OTHER WINDOW SIZES DON'T SEEM TO |
| | COMPLY WITH THE MIN. 24" CLEAR HEIGHT OPENING. REVISE |
| | PLANS AS REQUIRED. |
| | |
| | NOTE: ARCHITECT MAY BE CHARGED 4 TIMES THE PLAN REVIEW |
| | FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR |
| | MULTIPLE PLAN REVIEW REJECTIONS. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) EXTERIOR SWING DOORS AS SHOWN ON PLANS. NOA |
| | 01-0122.09 SUBMITTED EXPIRED ON APRIL 25, 2007. NEED |
| | CURRENT NOA. |
| | RESPONSE: NO PRODUCT APPROVAL SUBMITTED AT THIS TIME. |
| | NOTE: THIS MAY BE SUBMITTED AFTER PERMIT IS ISSUED, BUT |
| | BEFORE INSPECTIONS TO AVOID CONFLICT/DELAYS. |
| | |
| | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE. REPEAT COMMENT. |
| | |
| | 4- NEW SHEET T-1: |
| | A) THE CONSTRUCTION TYPE SPECIFIED UNDER THE LOCATION |
| | MAP IS INCORRECT. THIS IS A TYPE VB CONSTRUCTION NOT |
| | TYPE III. SEC. 602 FBC-5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) AS REQUESTED ON PREVIOUS CHECKLIST THE SCOPE OF WORK |
| | WAS REVISED TO SAY ALTERATION LEVEL 3 INSTEAD OF LEVEL |
| | 2. THIS WAS DONE, BUT THERE IS STILL REFERENCE FOR |
| | ALTERATION LEVEL 2 BELOW THE FRONT ELEVATION SHOWN ON |
| | THE UPPER RIGHT CORNER OF THIS DRAWING. CLARIFY/REVISE |
| | AS REQUIRED TO MATCH THE SCOPE OF WORK. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |