| 2017-09-06 16:07:57 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS A METER MAIN COMBO EXISTING |
| | FEEDING AN INTERIOR PANEL. PLAN SHOWS A METER AND PANEL |
| | ON EXTERIOR OF HOUSE. PROVIDE CORRECTION FOR |
| | DISCREPANCY. FBC 107.2.1; NEC 215.5 |
| | 2. IF THERE IS AN INTERIOR PANEL, WIRING TO THE |
| | INTERIOR PANEL MUST INCLUDE AN EQUIPMENT GROUNDING |
| | CONDUCTOR. SHOW LOCATION OF PANEL ON PLAN. NEC 250.122; |
| | FBC 107.2.1, FBC RE3704.6 |
| | 3. LOCATION OF INTERSYSTEM BONDING TERMINATION IS SHOWN |
| | AT THE INTERIOR PANEL. THIS SHOULD BE LOCATED AT MAIN |
| | SERVICE. PROVIDE CORRECTION. NEC 250.94; FBC RE3609.3 |
| | 4. NOTE # 9 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. ALSO, THE 2008 |
| | CODE IS CITED, WHICH IS NOT THE CURRENT CODE. PROVIDE |
| | CORRECTION. NEC 406.12; FBC PREFACE, FBC RE4002.14 |
| | 5. BREAKER FOR WATER HEATER IS STATED AS 50 AMP, WHICH |
| | IS TOO LARGE FOR THE LOAD OF 4500 WATTS SPECIFIED IN |
| | LOAD CALCULATION. BREAKER SHOULD BE SIZED AT 125% OF |
| | THE LOAD. PROVIDE CORRECTION. NEC 422.13; FBC RE3702.10 |
| | 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE3901.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |