Plan Review Notes
Plan Review Notes For Permit 17080634
Permit Number 17080634
Review Stop E
Sequence Number 1
Notes
Date Text
2017-09-06 16:07:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A METER MAIN COMBO EXISTING
 FEEDING AN INTERIOR PANEL. PLAN SHOWS A METER AND PANEL
 ON EXTERIOR OF HOUSE. PROVIDE CORRECTION FOR
 DISCREPANCY. FBC 107.2.1; NEC 215.5
 2. IF THERE IS AN INTERIOR PANEL, WIRING TO THE
 INTERIOR PANEL MUST INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. SHOW LOCATION OF PANEL ON PLAN. NEC 250.122;
 FBC 107.2.1, FBC RE3704.6
 3. LOCATION OF INTERSYSTEM BONDING TERMINATION IS SHOWN
 AT THE INTERIOR PANEL. THIS SHOULD BE LOCATED AT MAIN
 SERVICE. PROVIDE CORRECTION. NEC 250.94; FBC RE3609.3
 4. NOTE # 9 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ALSO, THE 2008
 CODE IS CITED, WHICH IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. NEC 406.12; FBC PREFACE, FBC RE4002.14
 5. BREAKER FOR WATER HEATER IS STATED AS 50 AMP, WHICH
 IS TOO LARGE FOR THE LOAD OF 4500 WATTS SPECIFIED IN
 LOAD CALCULATION. BREAKER SHOULD BE SIZED AT 125% OF
 THE LOAD. PROVIDE CORRECTION. NEC 422.13; FBC RE3702.10
 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  