Plan Review Notes
Plan Review Notes For Permit 17080610
Permit Number 17080610
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-14 08:14:41****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 RESIDENTIAL 905.2.7, TWO LAYERS OF UNDERLAYMENT
 REQUIRED:
  
 R905.2.7 UNDERLAYMENT APPLICATION.
 UNDERLAYMENT SHALL BE INSTALLED USING ONE OF THE
 FOLLOWING METHODS:
  
 1. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 UNDERLAYMENT SHALL COMPLY WITH ASTM D 226, TYPE I OR
 TYPE II OR ASTM D 4869, TYPE II OR TYPE IV OR ASTM D
 6757 AND SHALL BE TWO LAYERS APPLIED IN THE FOLLOWING
 MANNER. APPLY A 19-INCH (483 MM) STRIP OF UNDERLAYMENT
 FELT PARALLEL TO AND STARTING AT THE EAVES, FASTENED
 SUFFICIENTLY TO HOLD IN PLACE. STARTING AT THE EAVE,
 APPLY 36-INCH-WIDE (914 MM) SHEETS OF UNDERLAYMENT,
 OVERLAPPING SUCCESSIVE SHEETS 19 INCHES (483 MM), AND
 FASTENED WITH A 1-INCH (25 MM) ROUND PLASTIC CAP, METAL
 CAP NAILS OR NAILS AND TIN-TABS ATTACHED TO A NAILABLE
 DECK WITH ONE ROW IN THE FIELD OF THE SHEET WITH A
 MAXIMUM FASTENER SPACING OF 12 INCHES (305 MM) O.C.,
 AND ONE ROW AT THE OVERLAPS FASTENED 6 INCHES (152 MM)
 O.C. SYNTHETIC UNDERLAYMENT SHALL BE FASTENED IN
 ACCORDANCE WITH THIS SECTION AND THE MANUFACTURER?S
 RECOMMENDATIONS.
  
 A PRINT HOLD HAS BEEN PLACED ON THE PERMIT. OWNER
 BUILDER IS TO ACKNOWLEDGE THIS REQUIREMENT PRIOR TO
 PERMIT ISSUANCE.
  
  
  
  