| 2017-11-16 09:16:44 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17080590 |
| | ADD: 2740 S. DIXIE HWY. |
| | CONT: SOUTHEAST CERTIFIED CONSTRUCTION |
| | TEL: 561-818-4113 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. NOV. 16/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2A) SEMI-COMPLIED. THE COVERSHEET NOW INDICATES |
| | MERCANTILE AND S1 NON-SEPARATED MIXED USE. SHEET |
| | A010 STILL SHOWS AN S2 OCCUPANCY WHICH WILL REQUIRE A 1 |
| | HOUR FIRE SEPARATION. 107.2.1.3 ADDITIONAL INFORMATION |
| | , AND FBC-B TABLE 508.4. |
| | 1ST ROUND COMMENTS. THE COVERSHEET, T UNDER THE HEADING |
| | HEADINGS LIST THE OCCUPANCY AS MERCANTILE UNDER THE |
| | PROJECT CODE TABULAR AS MERCANTILE, REQUIRED SEPARATION |
| | NON SEPARATED MIXED USE. THE OTHER OCCUPANCY TYPE HAS |
| | NOT BEEN DECLARED EITHER A S1 OR A S2 OCCUPANCY. |
| | |
| | 2B2D) COMPLIED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) SHEET A100 SITE PLAN; |
| | 4A) SEMI-COMPLIED. THE PLANS DO NOT SHOW THE WIDTH FOR |
| | THE ACCESSIBLE PARKING SPACE NOR ACCESS AISLE. NOTE IT |
| | IS UNDER STOOD THAT THE PARKING LOT WAS NOT CONSIDERED |
| | PART OF THE PROJECT, BUT THE ACCESSIBILITY CODE |
| | REQUIRES ACCESS FROM THE PARKING LOT TO THE BUILDING ON |
| | AN ACCESSIBLE PATH. |
| | 2014 ACCESSIBILITY CODE 202.3 ALTERATIONS. WHERE |
| | EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE |
| | ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL |
| | COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2 |
| | AND SECTION 201.1.1. SEE SECTION 208.1 FOR EXISTING |
| | PARKING. |
| | 1ST ROUND OF COMMENTS. THE BOTTOM RIGHT HAND CORNER OF |
| | THE SHEET A TYPICAL PARKING DETAIL IS GIVEN WITH A |
| | WIDTH OF 9FOOT 6 INCHES CENTERLINE TO CENTER LINE |
| | PLEASE REVIEW THE CITY STANDARD FOUND WITHIN THE CITY |
| | OF WEST PALM BEACH MUNI CODE 94-485. |
| | |
| | 4B) 2ND REQUEST. THE SITE PLAN A100 INDICATES THE |
| | STRIPPING ON THE ACCESSIBLE PARKING SPACE IS 2 FEET |
| | WIDE, PLEASE REVIEW THE CITY OF WEST PALM BEACH MUNI |
| | ORDINANCE 94-485 STALL PAINTING DETAILS. |
| | ACCESS. CODE ADVISORY 502.3.3 MARKING. THE METHOD AND |
| | COLOR OF MARKING ARE NOT SPECIFIED BY THESE |
| | REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL |
| | LAWS OR REGULATIONS. |
| | 1ST ROUND OF COMMENTS. THE PLAN DOES NOT INDICATE WHICH |
| | SIDE OF THE BUILDING IS THE FRONT, WITH EXCEPTION TO |
| | THE NORTH ARROW MAKING THE BOTTOM OF THE PAGE THE FRONT |
| | OF THE BUILDING. NOTE NO STOP SIGN THIS SIDE OF THE |
| | STREET SEE COUNTY GIS, AND GOOGLE EARTH. THE ISSUE IS |
| | ALL OF THE PARKING SPACES ARE PROVIDED WITH CAR WHEEL |
| | STOPS, WITH EXCEPTION TO THE HANDICAPPED PARKING SPACE. |
| | THIS ALLOWS THE CAR TO PULL IN FURTHER INTO THE SPACE |
| | BLOCKING OFF ACCESS TO THE FRONT DOOR. THE |
| | ACCESSIBILITY CODE IN SECTION 208.3.1 REQUIRES AN |
| | ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES IN WIDTH. |
| | |
| | 4C) BUILDING PROVISO: A PERMIT FOR THE SEALING AND |
| | STRIPING OF THE PARKING LOT HAS TO BE APPLIED FOR, PAY |
| | FOUR TIMES THE FEE BEFORE THIS PERMIT CAN BE ISSUED. |
| | THE PARKING SEALING AND STRIPING PERMIT HAS TO BE |
| | FINALED BEFORE THIS PERMIT CAN APPLY FOR A FINAL |
| | INSPECTION. A HOLD WILL BE PUT ON THE BUILDING PERMITS |
| | FINAL INSPECTION. |
| | |
| | 1ST ROUND OF COMMENTS. GOOGLE EARTH SHOW THE PARKING |
| | LOT TO HAVE BEEN JUST RECENTLY RESTRIPED. ALSO IN THE |
| | SAME PHOTOGRAPH IS A RENTALS SIGN AVAILABLE!!! A SPATE |
| | PERMIT IS REQUIRED FOR RESTRIPING OF THE PARKING LOT |
| | AND A 4X FEE PUT ON THIS PROPERTY. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 105.1 REQUIRED. ANY CONTRACTOR, OWNER, |
| | OR AGENT AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE |
| | 489 WHO INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, |
| | MOVE, DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING |
| | OR STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER, |
| | REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT RESISTANT |
| | COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR |
| | FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD |
| | RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS |
| | REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE |
| | DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) THE FRONT COVER SHEET PROVIDES THE WIND DESIGN |
| | CRITERIA. SHEET A510 INDICATES THE PRESSURES ON SOME OF |
| | THE OPENINGS WITH A MEAN ROOF HEIGHT OF 16 FEET. THE |
| | DOUBLE DOOR PRESSURES ARE LOW FOR AN EXPOSURE C |
| | INTERIOR WALL ZONE (4) AT APPROX. 40 SQ. FT. THEY |
| | SHOULD BE AROUND +34.0/-41.4 PSF VASD. 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. |
| | |
| | 7) MISSING REQUIRED PRODUCT APPROVALS. 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS , ROLL UP DOORS |
| | |
| | NOA:17-0201.02 NO SHOP DRAWING STAMP OF APPROVAL / |
| | GLAZING, SIZE, ANCHORAGE, MULLIONS PRESSURES NOT |
| | IDENTIFIED. |
| | FL 742-R7 NO SHOP DRAWING STAMP OF APPROVAL/ PRESSURES |
| | NOT IDENTIFIED. |
| | |
| | (B) WINDOWS |
| | NOA 14-1112.06 NO SHOP DRAWING STAMP OF APPROVAL / |
| | GLAZING, SIZE, ANCHORAGE, MULLIONS PRESSURES NOT |
| | IDENTIFIED. |
| | |
| | 8) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 |
| | FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 9)COMPLIED. SHEET A310 THE DOOR SCHEDULE FOR DOORS 101 |
| | & 102 EXTERIOR DOORS NEEDS TO SHOW COMPLIANCE WITH; |
| | THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF |
| | PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH |
| | MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT |
| | DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| | |
| | 10) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 11) IMPACT FEES/ CHANGE OF OCCUPANCY |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | |