Plan Review Notes
Plan Review Notes For Permit 17080590
Permit Number 17080590
Review Stop P
Sequence Number 1
Notes
Date Text
2017-09-20 15:10:269/20/17 1ST PLUMBING REVIEW DENIED
  
 1) LAUNDRY TUB SHALL NOT BE WET VENTED THOUGH THE
 BATHROOM GROUP HORIZONAL WET VENT AND MUST HAVE ITS OWN
 VENT FBC-P 912.1
  
 2) DOMESTIC WATER PIPING SHOWS 3/4" WATER PIPING BUT
 PLUMBING FIXTURE SCHEDULE ON PO.1 SHOW TOILET COLD
 WATER SUPPLY TO BE 1". PLEASE CLARIFY FBC 107.2.1
  
 3) SHOW HAND SINKS AS BEING TEMPERED 110 DEGREES MAX
 AND COMPLIES WITH FBC-P SECTION 607
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  