| Plan Review Notes For Permit 17080590 |
| Permit Number |
17080590 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-20 15:10:26 | 9/20/17 1ST PLUMBING REVIEW DENIED | | | | | | 1) LAUNDRY TUB SHALL NOT BE WET VENTED THOUGH THE | | | BATHROOM GROUP HORIZONAL WET VENT AND MUST HAVE ITS OWN | | | VENT FBC-P 912.1 | | | | | | 2) DOMESTIC WATER PIPING SHOWS 3/4" WATER PIPING BUT | | | PLUMBING FIXTURE SCHEDULE ON PO.1 SHOW TOILET COLD | | | WATER SUPPLY TO BE 1". PLEASE CLARIFY FBC 107.2.1 | | | | | | 3) SHOW HAND SINKS AS BEING TEMPERED 110 DEGREES MAX | | | AND COMPLIES WITH FBC-P SECTION 607 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|