Plan Review Notes
Plan Review Notes For Permit 17080567
Permit Number 17080567
Review Stop G
Sequence Number 2
Notes
Date Text
2017-08-25 16:26:021) SECOND REQUEST, SUBMIT TWO COPIES OF A HOUSE PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1.
 2) SECOND REQUEST, THE TOTAL VALUATION DOES NOT MATCH
 PROPOSAL, WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 3) SECOND REQUEST, SUBMIT MANUFACTURE INSTALLATION
 MANUAL IN FULL AND THAT MATCH DRAWING**PLAN SHOW 199BTU
 AND SPEC SHOW MAX 150BTU, IDENTIFICATION (IFGC 401.5)
 4) SECOND REQUEST, SUBMIT MANUFACTURE SPEC AND
 INSTALLATION SHEETS MANUFACTURER?S SPECIFICATION FOR
 BBQ GRILL SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2014 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 561-805-6720
 [email protected]
  