2017-10-30 15:16:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOWS PER WPB
 UTILITIES DEPARTMENT. PLEASE PLACE NOTE ON PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 2. SHT. P-2.0 SHOWS ROOF DRAIN, OVER FLOW DRAINS AND
 RAIN WATER LEADERS SHT. P-3.0 SHOWS SCUPPER DRAIN AND
 EMERGENCY SCUPPERS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. PLEASE PROVIDE DETAIL MAIN SCUPPER AND EMERGENCY
 SCUPPER SHALL COMPLY WITH FBC PL TABLE 1106.7 AND
 1108.3
  
 4. SHT. P-2.0 SHOWS SQFT FOR ALL 4 OF THE ROOF DRAINS
 AS 2431SQFT SHT. P3.0 ONLY 3 SUPPERS ONLY 1 AT 3200SQFT
 1 AT 3100SQFT AND 1 AT 200SQFT PLEASE CLARIFY
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  