2017-08-16 15:56:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471. CIVIL PAGES ARE NOT SIGNED AND DATED.
  
 2. FBC B TABLE 1607.1(26), ROOFS SUBJECT TO MAINTENANCE
 WORKERS TO BE DESIGNED TO 300# CONCENTRATED LIVE LOAD.
 EITHER REVISE PLAN AND CALCULATIONS ACCORDINGLY OR
 CONTACT ME TO DISCUSS.
  
  