| Plan Review Notes For Permit 17080546 |
| Permit Number |
17080546 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-16 15:56:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS, FS471. CIVIL PAGES ARE NOT SIGNED AND DATED. | | | | | | 2. FBC B TABLE 1607.1(26), ROOFS SUBJECT TO MAINTENANCE | | | WORKERS TO BE DESIGNED TO 300# CONCENTRATED LIVE LOAD. | | | EITHER REVISE PLAN AND CALCULATIONS ACCORDINGLY OR | | | CONTACT ME TO DISCUSS. | | | | | | |
|