Plan Review Notes
Plan Review Notes For Permit 17080542
Permit Number 17080542
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-14 11:46:241) SHOW THE SHOWER ON BOTH SETS OF PLANS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) THE SHOWER SHALL BE A MINIMUM OF 30 INCHES WIDE AND
 SHALL BE A MINIMUM OF 900 SQUARE INCHES. SHOW THE
 LENGTH AND WIDTH DIMENSIONS OF THE SHOWER ON BOTH SETS
 OF PLANS.
 3) THE SHOWER VALVE SHALL COMPLY WITH 2014 FPC
 SEC.424.3.
 4) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 5) SUBMIT A PLUMBING APPLICATION FROM A LICENSED
 PLUMBING CONTRACTOR FOR THE PUMBING WORK TO BE DONE.
 FL. STATUTE 489.105.
  