Plan Review Notes
Plan Review Notes For Permit 17080539
Permit Number 17080539
Review Stop B
Sequence Number 1
Notes
Date Text
2017-09-13 10:41:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SHEET SD01 DESIGN CRITIERA IS 170MPH EXPOSURE C, BUT
 GATE HAS PROPOSED DESIGN CRITERIA OF 115MPH. REVISE
 COVER PAGE (SD01) TO CLARIFY DESIGN CRITERIA, FBC 107,
 FBC B 1609.
  
 2. FBC B 1609, FBC 107, CALCULATIONS FOR ROLLING GATE
 ARE FOR 115 MPH. SD10 DECLARES 170MPH EXPOSURE C AND
 ALSO STATES THAT "GATE SHALL REMAIN IN OPEN SECURED
 POSITION DURING WINDSTORM EVENTS WITH SUSTAINED WINDS
 OVER 115 MPH".
  
 REVISE PLAN TO INDICATE CODE SECTION WHICH ALLOWS THIS
 WIND DESIGN.
  
 REVISE CALCULATIONS TO BE CONSISTENT WITH THE WIND
 DESIGN CRITERIA ON THE PLAN.
  
 CLARIFY HOW THIS WILL BE ENFORCED. HOW WILL OTHERS
 (MANAGEMENT, FUTURE MANAGEMENT, FUTURE OWNERS) KNOW
 THAT THE GATE MUST BE SECURED? THIS IS NOT A TYPICAL
 DESIGN.
  
  
  