| Plan Review Notes For Permit 17080539 |
| Permit Number |
17080539 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-13 10:41:06 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SHEET SD01 DESIGN CRITIERA IS 170MPH EXPOSURE C, BUT | | | GATE HAS PROPOSED DESIGN CRITERIA OF 115MPH. REVISE | | | COVER PAGE (SD01) TO CLARIFY DESIGN CRITERIA, FBC 107, | | | FBC B 1609. | | | | | | 2. FBC B 1609, FBC 107, CALCULATIONS FOR ROLLING GATE | | | ARE FOR 115 MPH. SD10 DECLARES 170MPH EXPOSURE C AND | | | ALSO STATES THAT "GATE SHALL REMAIN IN OPEN SECURED | | | POSITION DURING WINDSTORM EVENTS WITH SUSTAINED WINDS | | | OVER 115 MPH". | | | | | | REVISE PLAN TO INDICATE CODE SECTION WHICH ALLOWS THIS | | | WIND DESIGN. | | | | | | REVISE CALCULATIONS TO BE CONSISTENT WITH THE WIND | | | DESIGN CRITERIA ON THE PLAN. | | | | | | CLARIFY HOW THIS WILL BE ENFORCED. HOW WILL OTHERS | | | (MANAGEMENT, FUTURE MANAGEMENT, FUTURE OWNERS) KNOW | | | THAT THE GATE MUST BE SECURED? THIS IS NOT A TYPICAL | | | DESIGN. | | | | | | | | | |
|