| Plan Review Notes For Permit 17080529 |
| Permit Number |
17080529 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-12-27 07:52:53 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSES | | | SATISFACTORILY EXCEPT NUMBER 3 SHOWN BELOW. THE PERMIT | | | APPLICATION WAS SUBMITTED DURING THE TIME THAT THE 2014 | | | FLORIDA BUILDING CODE IS IN EFFECT, WHICH REFERENCES | | | THE 2011 NEC. PROVIDE CORRECTION TO SHOW THE DESIGN IS | | | TO THE 2011 NEC. | | | | | | 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION | | | SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE. | | | PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD | | | INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC | | | PREFACE, NEC 517.13 | | | | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|