| Notes |
| Date |
Text |
| 2017-10-24 13:21:08 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080514 | | | 10/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN RESPONSE TO THE PREVIOUS REVIEW COMMENT REQUIRING | | | EACH PRESSURIZATION FAN TO BE EQUIPPED WITH TWO BELTS, | | | THE ENGINEER OF RECORD HAS PROVIDED A RESPONSE AND ALSO | | | PLACED NOTES ON THE PLAN STATING THAT THE BELT DRIVES | | | ON THE FANS WILL BE MODIFIED IN THE FIELD TO ACCOMODATE | | | THE REQUIRED TWO BELTS ON THE PULLEY. | | | IN ORDER FOR THE PROPOSED MODIFICATION TO BE APPROVED, | | | PLEASE PROVIDE THE FOLLOWING ITEMS: | | | | | | A) MANUFACTURER'S PRODUCT SUBMITTAL FOR THE FAN MODEL | | | THAT IS FACTORY EQUIPPED WITH TWO BELTS. | | | B) MODIFICATION INSTRUCTIONS FROM THE MANUFACTURER'S | | | TECHNICAL DEPARTMENT TO CONVERT THE SINGLE-BELTED FANS | | | IN THE FIELD. | | | C) A LETTER FROM THE MANUFACTURER'S TECHNICAL | | | DEPARTMENT AUTHORIZING AND OUTLINING THE FIELD | | | MODIFICATION AND TESTING PROCESS. | | | D) A LETTER FORM THE MANUFACTURER STATING THAT THE | | | WARRANTIES FOR THE FANS WILL REMAIN INTACT. | | | E) SHOP DRAWING STAMPS ON THE MANUFACTURER'S SUBMITTALS | | | BY THE ENGINEER OF RECORD JOHN T.BOYER P.E, AND A | | | SIGNED AND SEALED LETTER FROM BOYER CERTIFYING THE | | | PROPOSED MODIFICATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|