2017-10-24 13:10:203RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17080513
 10/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE PREVIOUS REVIEW COMMENT REQUIRING
 EACH PRESSURIZATION FAN TO BE EQUIPPED WITH TWO BELTS,
 THE ENGINEER OF RECORD HAS PROVIDED A RESPONSE AND ALSO
 PLACED NOTES ON THE PLAN STATING THAT THE BELT DRIVES
 ON THE FANS WILL BE MODIFIED IN THE FIELD TO ACCOMODATE
 THE REQUIRED TWO BELTS ON THE PULLEY.
 IN ORDER FOR THE PROPOSED MODIFICATION TO BE APPROVED,
 PLEASE PROVIDE THE FOLLOWING ITEMS:
  
 A) MANUFACTURER'S PRODUCT SUBMITTAL FOR THE FAN MODEL
 THAT IS FACTORY EQUIPPED WITH TWO BELTS.
 B) MODIFICATION INSTRUCTIONS FROM THE MANUFACTURER'S
 TECHNICAL DEPARTMENT TO CONVERT THE SINGLE-BELTED FANS
 IN THE FIELD.
 C) A LETTER FROM THE MANUFACTURER'S TECHNICAL
 DEPARTMENT AUTHORIZING AND OUTLINING THE FIELD
 MODIFICATION AND TESTING PROCESS.
 D) A LETTER FORM THE MANUFACTURER STATING THAT THE
 WARRANTIES FOR THE FANS WILL REMAIN INTACT.
 E) SHOP DRAWING STAMPS ON THE MANUFACTURER'S SUBMITTALS
 BY THE ENGINEER OF RECORD JOHN T.BOYER P.E, AND A
 SIGNED AND SEALED LETTER FROM BOYER CERTIFYING THE
 PROPOSED MODIFICATION.
  