2017-10-17 11:33:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17080513
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE STAIR PRESSURIZATION FANS SHALL HAVE 1.5 TIMES
 THE NUMBER OF BELTS REQUIRED FOR THE DESIGN DUTY WITH
 THE MINIMUM NUMBER OF BELTS BEING TWO- SECTION
 513.10.5.
  