2017-08-16 08:29:091ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080513
 8/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED CURB FLASHING DETAIL FROM RAY
 ENGINEERING DOES NOT APPEAR TO BE COMPATIBLE WITH THE
 FAN SUBMITTAL FROM REVERSOMATIC WHICH SHOWS THE FAN
 SUPPORT LEGS ATTACHED TO A CONCRETE BASE. IN ADDITION
 THE ENGINEERING SUBMITTAL IS A COPY OF AN ORIGINAL
 SUBMITTAL BEARING A 10/27/15 DATE. PLEASE SEE SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE WHICH REQUIRES
  
 ENGINEERS TO PROVIDE ORIGINAL SIGNATURES AND SEALS TO
 CERTIFY THEIR WORK. ALSO LACKING FROM THE SUBMITTAL IS
 THE ENGINEER'S WIND DESIGN CRITERIA FOR INSTALLATION OF
 THE FANS- WIND SPEED, EXPOSURE CATEGORY, RISK CATEGORY,
 HEIGHT ABOVE GRADE, DESIGN PRESSURES ETC.- SEE SECTION
 1609 FBC-14 BUILDING.
  
 2) ADDITIONAL CONFLICTS IN THIS SUBMITTAL: A) THE
 PERMIT APPLICATION INDICATES 3 FANS TO BE REPLACED BUT
 THE REVERSOMATIC SUBMITTAL HAS HANDWRITTEN NOTES THAT
 APPEAR TO INDICATE 7 FANS WILL BE INSTALLED. B) THE
 SUBMITTAL FROM RAY ENGINEERING INDICATES THE FANS WILL
 HAVE TOTAL CAPACITIES OF 20,000 CFMS, HOWEVER THE
 SUBMITTAL FROM REVERSOMATIC INDICATES THE FANS WILL
 EITHER BE 10,000
  
 OR 14,000 CFMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  