| 2017-08-16 08:29:09 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17080513 |
| | 8/16/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED CURB FLASHING DETAIL FROM RAY |
| | ENGINEERING DOES NOT APPEAR TO BE COMPATIBLE WITH THE |
| | FAN SUBMITTAL FROM REVERSOMATIC WHICH SHOWS THE FAN |
| | SUPPORT LEGS ATTACHED TO A CONCRETE BASE. IN ADDITION |
| | THE ENGINEERING SUBMITTAL IS A COPY OF AN ORIGINAL |
| | SUBMITTAL BEARING A 10/27/15 DATE. PLEASE SEE SECTION |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE WHICH REQUIRES |
| | |
| | ENGINEERS TO PROVIDE ORIGINAL SIGNATURES AND SEALS TO |
| | CERTIFY THEIR WORK. ALSO LACKING FROM THE SUBMITTAL IS |
| | THE ENGINEER'S WIND DESIGN CRITERIA FOR INSTALLATION OF |
| | THE FANS- WIND SPEED, EXPOSURE CATEGORY, RISK CATEGORY, |
| | HEIGHT ABOVE GRADE, DESIGN PRESSURES ETC.- SEE SECTION |
| | 1609 FBC-14 BUILDING. |
| | |
| | 2) ADDITIONAL CONFLICTS IN THIS SUBMITTAL: A) THE |
| | PERMIT APPLICATION INDICATES 3 FANS TO BE REPLACED BUT |
| | THE REVERSOMATIC SUBMITTAL HAS HANDWRITTEN NOTES THAT |
| | APPEAR TO INDICATE 7 FANS WILL BE INSTALLED. B) THE |
| | SUBMITTAL FROM RAY ENGINEERING INDICATES THE FANS WILL |
| | HAVE TOTAL CAPACITIES OF 20,000 CFMS, HOWEVER THE |
| | SUBMITTAL FROM REVERSOMATIC INDICATES THE FANS WILL |
| | EITHER BE 10,000 |
| | |
| | OR 14,000 CFMS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |