| 2017-10-24 16:20:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE 2 COPIES OF ELECTRICAL PLAN FOR REVIEW. FBC |
| | 107.2.1, 107.3.5 (PLAN MUST BE SIGNED BY PERSON |
| | RESPONSIBLE FOR THE DESIGN. SHOW ELECTRICAL WIRING AND |
| | OUTLETS PER CODE.) |
| | 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE. |
| | SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING |
| | OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3, |
| | FBC 107.2.1 (NOT PROVIDED). |
| | 3. SHOW OUTLETS ON PLAN TO COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1 |
| | (NOT PROVIDED.) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |