| 2017-09-14 12:27:11 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17080495 |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. SUITE: UNIT14A |
| | CONT: SUFFOLK |
| | TEL: 561-407-496-3168 ED HANRATTY |
| | E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS |
| | E-MAIL ADDRESS REQUIREMENTS, |
| | WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN |
| | RECORD. |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | SUBJECT TO FAIR HOUSING! |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY SEPT. 14/2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 126.33_A2-90-14A. THE PANTRY MEASURES 4 FT. 8 |
| | INCHES IN DEPTH. WHEN CLOSETS ARE OVER 2 FEET IN DEPTH |
| | THE DOOR NEEDS TO MEASURE 32 INCHES IN THE CLEAR. FAIR |
| | HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 FBC- |
| | ACCESSIBILITY/ FAIR HOUSING SECTION 100.205.(C)(2)(2). |
| | |
| | 2) SHEET 242.33-A6-66-14A. FLOOR FINISHES. . BLDG TYPE: |
| | TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR |
| | PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF |
| | THERE IS A DROP CEILING WITH OR WITHOUT INSULATION: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56A, A6.13A & |
| | A7.55A AS CUSTOM UNIT SUPPLEMENTAL INDEX AND ADDED |
| | REFERENCE NOTES, BUT THESE SHEETS ARE NOT PART OF THE |
| | PLAN SET SUBMITTED? THEN WHY ARE THESE SHEETS LISTED IN |
| | THE INDEX FOR THIS UNIT? 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |