| 2017-08-18 11:02:02 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THE MEMBRANE MATERIAL OF THE AWNING SHALL MEET THE |
| | REQUIREMENTS OF THE CODE. |
| | |
| | 25.5 PERMANENT MEMBRANE STRUCTURES. |
| | 25.5.1 APPLICATION. |
| | 25.5.1.1 USE OF MEMBRANE ROOFS. MEMBRANE ROOFS SHALL BE |
| | USED IN ACCORDANCE WITH THE FOLLOWING: |
| | (1) MEMBRANE MATERIALS SHALL NOT BE USED WHERE FIRE |
| | RESISTANCE RATINGS ARE REQUIRED FOR WALLS OR ROOFS. |
| | (2) WHERE EVERY PART OF THE ROOF, INCLUDING THE ROOF |
| | MEMBRANE, IS NOT LESS THAN 20 FT (6100 MM) ABOVE ANY |
| | FLOOR, BALCONY, OR GALLERY, A NONCOMBUSTIBLE OR |
| | LIMITEDCOMBUSTIBLE MEMBRANE SHALL BE PERMITTED TO BE |
| | USED AS THE ROOF IN ANY CONSTRUCTION TYPE. |
| | (3) WITH APPROVAL OF THE AHJ, MEMBRANE MATERIALS SHALL |
| | BE PERMITTED TO BE USED WHERE EVERY PART OF THE ROOF |
| | MEMBRANE IS SUFFICIENTLY ABOVE EVERY SIGNIFICANT FIRE |
| | POTENTIAL, SUCH THAT THE IMPOSED TEMPERATURE CANNOT |
| | EXCEED THE CAPABILITY OF THE MEMBRANE, INCLUDING SEAMS, |
| | TO MAINTAIN ITS STRUCTUAL INTEGRITY. |
| | |
| | |
| | 25.5.1.5 FLAME PROPAGATION PERFORMANCE. |
| | 25.5.1.5.1 ALL MEMBRANE STRUCTURE FABRIC SHALL MEET THE |
| | FLAME PROPAGATION PERFORMANCE CRITERIA CONTAINED IN |
| | NFPA 701, STANDARD METHODS OF FIRE TESTS FOR FLAME |
| | PROPAGATION OF TEXTILES AND FILMS. [101:11.9.1.6.1] |
| | |
| | |