| 2017-08-16 06:40:03 | 1) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE CSST OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3. |
| | 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2014 FBC-FUEL |
| | GAS SEC.409.4. |
| | 3) SHOW THE DISTANCE FROM EACH MP REGULATOR TO THE MOST |
| | REMOTE OUTLET IN THE BRANCH LINE PER THE 2014 FBC-FUEL |
| | GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| | 4) SHOW THE CORRESPONDING EHD NUMBER FOR EACH SIZE OF |
| | CSST. 2014 FBC-FUEL GAS 402.4. |
| | 5) THE CSST ON THE SYSTEM APPEARS TO BE UNDERSIZED BUT |
| | WITHOUT KNOWING WHICH SIZING TABLE IS BEING USED, A |
| | COMPREHENSIVE REVIEW COULD NOT BE DONE. ADDITIONAL PLAN |
| | REVIEW COMMENTS MAY BE FORTHCOMING UPON A SUBSEQUENT |
| | REVIEW. |
| | 6) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014 |
| | FBC-FUEL GAS SEC. 301.3. SUBMIT COPIES OF |
| | MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| | APPLIANCES/EQUIPMENT SHOWING COMPLIANCE. |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP |
| | REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION. |
| | 2014 FGC SEC. 410.1. |
| | 8) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES. 2014 FGC SEC.304.1. |
| | 9) PE PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND |
| | ONLY. 2014 FGC SEC.404.17.1. |
| | 10) THE LOCATION OF ALL GAS VENTS SHALL COMPLY WITH |
| | 2014 FBC-FUEL GAS SECS. 502 THRU 505 OR 2014 FBC-RES. |
| | SEC.G2426. |
| | |