| Plan Review Notes For Permit 17080446 |
| Permit Number |
17080446 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-10-10 12:34:02 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080446 | | | 10/10/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #2 FROM THE PREVIOUS REVIEW WAS NOT | | | ADDRESSED AND STILL EXISTS. I HAVE REPRINTED IT BELOW. | | | | | | M2: THE WIND DESIGN CRITERIA USING ULTIMATE WIND SPEED | | | OF 140 MPH BASED ON THE ASCE 7-05 IS OUTDATED- SEE | | | SECTION1609.1.1 FBC-14 BUILDING. THE ULTIMATE WIND | | | SPEED FOR WEST PALM BEACH IS 170 MPH BASED ON THE | | | CURRENT EDITION OF ASCE 7-2010- PLEASE CORRECT. | | | | | | 2) NEW COMMENT: THE DIRECTIONAL ARROWS FOR THE AIRFLOW | | | OF THE RETURN AIR DUCTWORK ARE POINTING IN THE WRONG | | | DIRECTION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|