| Plan Review Notes For Permit 17080446 |
| Permit Number |
17080446 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-09-14 17:36:32 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080446 | | | 9/14/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: CLARIFY HOW MAKEUP WILL BE PROVIDED FOR | | | THE EXHAUST VENTILATION SYSTEM IN THE TRAINING ROOM | | | WHICH IS REQUIRED TO RUN CONTINUOUSLY WHEN THE ROOM IS | | | OCCUPIED- SEE SECTION 501.4. | | | | | | 2) M2: THE WIND DESIGN CRITERIA USING ULTIMATE WIND | | | SPEED OF 140 MPH BASED ON THE ASCE 7-05 IS OUTDATED- | | | SEE SECTION1609.1.1 FBC-14 BUILDING. THE ULTIMATE WIND | | | SPEED FOR WEST PALM BEACH IS 170 MPH BASED ON THE | | | CURRENT EDITION OF ASCE 7-2010. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|