Plan Review Notes
Plan Review Notes For Permit 17080446
Permit Number 17080446
Review Stop E
Sequence Number 2
Notes
Date Text
2017-09-18 11:08:55CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENT NOT ADDRESSED:
 2. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5
 (PROVIDE CALCULATION SHOWING THE ALLOWED WATTAGE FOR
 THE AREA AND THE PROPOSED WATTAGE TO BE INSTALLED, IN
 COMPLIANCE WITH CODE.)
  
 NEW COMMENT:
 1. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. THERE
 SHOULD NOT BE A SEPARATE CIRCUIT FOR THESE ITEMS.
 PROVIDE CORRECTION. NEC 700.12(F)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  