| Plan Review Notes For Permit 17080446 |
| Permit Number |
17080446 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-09-18 11:08:55 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENT NOT ADDRESSED: | | | 2. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5 | | | (PROVIDE CALCULATION SHOWING THE ALLOWED WATTAGE FOR | | | THE AREA AND THE PROPOSED WATTAGE TO BE INSTALLED, IN | | | COMPLIANCE WITH CODE.) | | | | | | NEW COMMENT: | | | 1. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. THERE | | | SHOULD NOT BE A SEPARATE CIRCUIT FOR THESE ITEMS. | | | PROVIDE CORRECTION. NEC 700.12(F) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|