2017-08-22 09:16:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080446
 8/22/17
  
 1) EXHAUST VENTILATION AT A RATE OF 0.5 CFMS PER SQ.
 FT. IS REQUIRED FOR THE BARBER SHOP AREA- TABLE 403.3.
 PLEASE PROVIDE A SYSTEM AND REVISE THE PLANS AND THE
 AIR BALANCE CALCULATIONS ACCORDINGLY.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM OF THE NEW RTU- SECTION 606.2.1
  
 4) REFER TO SECTION 301.15 AND PROVIDE ENGINEERED
 STRUCTURAL DETAILS FOR INSTALLATION OF THE NEW RTU
 INCLUDING THE ROOF OPENING AND REINFORCEMENTS, CURB AND
 RTU ATTACHMENTS. PLEASE INCLUDE THE WIND LOAD DESIGN
 CRITERIA AS SPECIFIED IN SECTION 1609 FBC-14 BUILDING.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RTU.
  