| 2017-08-22 09:16:37 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080446 | | | 8/22/17 | | | | | | 1) EXHAUST VENTILATION AT A RATE OF 0.5 CFMS PER SQ. | | | FT. IS REQUIRED FOR THE BARBER SHOP AREA- TABLE 403.3. | | | PLEASE PROVIDE A SYSTEM AND REVISE THE PLANS AND THE | | | AIR BALANCE CALCULATIONS ACCORDINGLY. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW RTU- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | | | 3) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR | | | SYSTEM OF THE NEW RTU- SECTION 606.2.1 | | | | | | 4) REFER TO SECTION 301.15 AND PROVIDE ENGINEERED | | | STRUCTURAL DETAILS FOR INSTALLATION OF THE NEW RTU | | | INCLUDING THE ROOF OPENING AND REINFORCEMENTS, CURB AND | | | RTU ATTACHMENTS. PLEASE INCLUDE THE WIND LOAD DESIGN | | | CRITERIA AS SPECIFIED IN SECTION 1609 FBC-14 BUILDING. | | | | | | 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RTU. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|