| 2017-08-14 12:02:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) SHEET M1 - A 3,000 CFM A/C UNIT IS PROPOSED. A DUCT |
| | DETECTOR IS NOT READILL INDICATED OR NOTED. |
| | PER NFPA NFPA 90A, STANDARD FOR THE INSTALLATION OF |
| | AIR-CONDITIONING AND VENTILATING SYSTEMS, 2012 EDITION. |
| | |
| | CHAPTER 6 CONTROLS |
| | 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL. |
| | 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE |
| | TESTED AT LEAST ANNUALLY. |
| | 6.4.2* LOCATION. |
| | 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR |
| | DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: |
| | (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY |
| | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A |
| | CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN) |
| | (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON |
| | RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR |
| | INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A |
| | CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND |
| | SERVING MORE THAN ONE STORY |
| | |
| | |
| | PLEASE ENSURE THE REQUIREMENT IS MET AND PROVIDE THE |
| | APPLICABLE REVISION PRIOR TO FIRE FINAL. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |