2017-08-14 12:02:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET M1 - A 3,000 CFM A/C UNIT IS PROPOSED. A DUCT
 DETECTOR IS NOT READILL INDICATED OR NOTED.
 PER NFPA NFPA 90A, STANDARD FOR THE INSTALLATION OF
 AIR-CONDITIONING AND VENTILATING SYSTEMS, 2012 EDITION.
  
 CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
  
 PLEASE ENSURE THE REQUIREMENT IS MET AND PROVIDE THE
 APPLICABLE REVISION PRIOR TO FIRE FINAL.
  
  
 PETER LEDUC
 FIRE MARSHAL