| Plan Review Notes For Permit 17080446 |
| Permit Number |
17080446 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-15 14:49:34 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | | SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT | | | NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA, | | | WIRELESS SYSTEMS, KITCHEN HOODS ETC. FBC 105.1 | | | 2. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5 | | | 3. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED | | | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW A | | | TIMECLOCK CONTROLLED CIRCUIT OR AN OCCUPANCY SENSORS. | | | FBC C405.2.2, 405.2.2.2 | | | 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC C405.7.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|