| 2017-10-10 15:00:57 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | ITEMS CORRECTED HAVE BEEN NOTED, REMAINING COMMENTS |
| | NEED FURTHER CORRECTION. |
| | |
| | 1. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 (THERE IS A NOTE |
| | BETWEEN THE FIRST FLOOR AND SECOND FLOOR LAYOUT THAT |
| | STILL STATES THE WRONG CODE.) |
| | 2. CORRECTED. |
| | 3. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER |
| | SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE, AND THAT OUTLETS SHALL BE INSTALLED IN |
| | ANY COUNTER SPACE THAT IS 12 INCHES OR WIDER. THE PLAN |
| | PROVIDED DOES NOT MEET THIS CODE IN SOME AREAS. PROVIDE |
| | CORRECTION. NEC 210.52(C)(1); FBC RE3901.4 (WALL |
| | SPACING OF OUTLETS IS STILL NOT CORRECT, WITH MORE THAN |
| | 4 FEET BETWEEN OUTLETS IN SOME LOCATIONS.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. PROVIDE ACCURATE LOAD CALCULATION. LOAD CALC |
| | PROVIDED SHOWS A COMPARISON FOR 2 DIFFERENT A/C |
| | SYSTEMS, BUT ONLY ONE IS SHOWN ON PLAN. IS THERE ONLY |
| | ONE SYSTEM, OR TWO? THE AHU UNIT IS STATED AS A 10KW |
| | LOAD, BUT ONLY 3500 IS INCLUDED IN THE CALCULATION. THE |
| | LARGER OF THE LOADS IS REQUIRED TO BE USED. THE AHU FAN |
| | SHOULD BE INCLUDED WITH THE AHU TOTAL LOAD, NOT A |
| | SEPARATE LOAD. NEC 220; FBC RE 3602.2 (LOAD CALCULATION |
| | IS INCORRECT AND DOES NOT MATCH EQUIPMENT SPECIFIED ON |
| | THE MECHANICAL PLAN. SEE FBC RESIDENTIAL FOR |
| | EXPLANATION OF A CORRECT LOAD CALCULATION.) |
| | 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 (THIS BONDING POINT |
| | IS NOT LOCATED INSIDE THE METER CAN. SEE NEC 250.94 OR |
| | FBC RE 3609.3) |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |