Plan Review Notes
Plan Review Notes For Permit 17080434
Permit Number 17080434
Review Stop E
Sequence Number 2
Notes
Date Text
2017-10-10 15:00:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 ITEMS CORRECTED HAVE BEEN NOTED, REMAINING COMMENTS
 NEED FURTHER CORRECTION.
  
 1. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14 (THERE IS A NOTE
 BETWEEN THE FIRST FLOOR AND SECOND FLOOR LAYOUT THAT
 STILL STATES THE WRONG CODE.)
 2. CORRECTED.
 3. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE, AND THAT OUTLETS SHALL BE INSTALLED IN
 ANY COUNTER SPACE THAT IS 12 INCHES OR WIDER. THE PLAN
 PROVIDED DOES NOT MEET THIS CODE IN SOME AREAS. PROVIDE
 CORRECTION. NEC 210.52(C)(1); FBC RE3901.4 (WALL
 SPACING OF OUTLETS IS STILL NOT CORRECT, WITH MORE THAN
 4 FEET BETWEEN OUTLETS IN SOME LOCATIONS.)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. PROVIDE ACCURATE LOAD CALCULATION. LOAD CALC
 PROVIDED SHOWS A COMPARISON FOR 2 DIFFERENT A/C
 SYSTEMS, BUT ONLY ONE IS SHOWN ON PLAN. IS THERE ONLY
 ONE SYSTEM, OR TWO? THE AHU UNIT IS STATED AS A 10KW
 LOAD, BUT ONLY 3500 IS INCLUDED IN THE CALCULATION. THE
 LARGER OF THE LOADS IS REQUIRED TO BE USED. THE AHU FAN
 SHOULD BE INCLUDED WITH THE AHU TOTAL LOAD, NOT A
 SEPARATE LOAD. NEC 220; FBC RE 3602.2 (LOAD CALCULATION
 IS INCORRECT AND DOES NOT MATCH EQUIPMENT SPECIFIED ON
 THE MECHANICAL PLAN. SEE FBC RESIDENTIAL FOR
 EXPLANATION OF A CORRECT LOAD CALCULATION.)
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3 (THIS BONDING POINT
 IS NOT LOCATED INSIDE THE METER CAN. SEE NEC 250.94 OR
 FBC RE 3609.3)
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  