2017-09-01 11:21:14PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 PLAN DOES NOT SHOW WHERE RETURN AIR DUCT IS GOING
 OR SIZE. 2014 RESIDENTIAL CODE
 2) PROVIDE ENERGY CALCULATIONS FOR BUILDING # 2.
 SECTION M1401.3 SIZING 2014 RESIDENTIAL CODE
 3) ENERGY CALCULATIONS AND PLAN DO NOT MATCH
  