2017-08-28 16:14:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 2. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD. PROVIDE CORRECTION. NEC 422.13; FBC
 RE3702.10
 3. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE, AND THAT OUTLETS SHALL BE INSTALLED IN
 ANY COUNTER SPACE THAT IS 12 INCHES OR WIDER. THE PLAN
 PROVIDED DOES NOT MEET THIS CODE IN SOME AREAS. PROVIDE
 CORRECTION. NEC 210.52(C)(1); FBC RE3901.4
 4. PROVIDE DISCONNECTING MEANS ON THE EXTERIOR OF THE
 BUILDING AT THE SERVICE LOCATION FOR THE ELECTRICAL
 PANEL. SERVICE CONDUCTORS ARE NOT PERMITTED TO BE
 INSIDE THE BUILDING WITHOUT OVER CURRENT PROTECTION.
 NEC 230.71(A)(1); FBC RE3601.6.2
 5. NOTE FOR AFCI PROTECTION STATES THAT ALL OUTLETS IN
 BEDROOMS SHALL HAVE AFCI PROTECTION. CODE STATES: "ALL
 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION." PROVIDE CORRECTION. NEC 210.12; FBC
 RE3902.12
 6. NOTE FOR ENERGY COMPLIANCE STATES THAT "50% OF LAMPS
 SHALL BE 75% EFFICIENT". CODE STATES: "A MINIMUM OF 75
 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF
 75 PERCENT OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY LAMPS".
 PROVIDE CORRECTION. A NOTE WILL SUFFICE. FBC CE R404.1
 7. PROVIDE ACCURATE LOAD CALCULATION. LOAD CALC
 PROVIDED SHOWS A COMPARISON FOR 2 DIFFERENT A/C
 SYSTEMS, BUT ONLY ONE IS SHOWN ON PLAN. IS THERE ONLY
 ONE SYSTEM, OR TWO? THE AHU UNIT IS STATED AS A 10KW
 LOAD, BUT ONLY 3500 IS INCLUDED IN THE CALCULATION. THE
 LARGER OF THE LOADS IS REQUIRED TO BE USED. THE AHU FAN
 SHOULD BE INCLUDED WITH THE AHU TOTAL LOAD, NOT A
 SEPARATE LOAD. NEC 220; FBC RE 3602.2
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 9. PROVIDE DETAIL OF METHOD TO DETERMINE THE 25 OHM
 RESISTANCE REQUIRED ON THE GROUND ROD, OR SHOW THE
 ADDITION OF A SUPPLEMENTAL ELECTRODE. NEC 250.53(A)(2);
 FBC RE 3608.4
 10. RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION FOR DEN. NEC 210.52; FBC RE3901.2.1
 11. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE NOTE FOR
 COMPLIANCE. NEC 410.16; FBC RE4003.12
 12. ADDRESS LISTED ON RISER DIAGRAM STATES THIS IS FOR
 345 MARLBOROUGH PLACE. PROVIDE CORRECTION. FBC 107.2.1
 13. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. BE ADVISED THAT IF ROMEX IS USED,
 THE AMPACITY RATING FOR #8 ROMEX IS 40 AMPS AND FOR #6
 ROMEX IS 50 AMPS. NEC 210.8, 210.12, 215.5, 334.80,
 408.4; FBC RE3706.2, RE3902, RE3705.4.4
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  