2018-02-02 17:26:12RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE NOT
 ACCEPTABLE. THEY ARE NOT DONE WITH AN APPROVED METHOD.
 NEED TO PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS
 BASED ON THE ORIENTATION OF THE BUILDING AS REQUIRED BY
 SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: PLEASE MAKE SURE EQUIPMENT LISTED IN THE
 EQUIPMENT SIZING CALCULATIONS MATCHES EQUIPMENT LISTED
 IN THE A/C PLAN TO AVOID CONFLICTS/DELAYS.
  