2018-02-02 15:15:27RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) COOLING SYSTEM AND EFFICIENCY SPECIFIED ON ITEM #12A
 AND 12B DON'T MATCH PLANS. THERE IS NO DUCTLESS MINI
 SPLIT UNIT SPECIFIED ON PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.1 FBC -ENERGY CONSERVATION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMITTING OFFICE. SEC.
 R101.5.1.1.1 FBC -ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) WINDOW AREA SPECIFIED ON ITEM #6(C) DOESN'T MATCH
 PLANS. NOTE: THERE ARE TWO WINDOWS SHOWN ON PLANS. SEE
 PLAN FOR SIZES AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.1 FBC -ENERGY CONSERVATION.
  
 D) REVISE ITEM #9. WALL TYPE IS MASONRY NOT WOOD FRAME.
 CALCULATIONS NEED TO SHOW THE R-4.1 INSULATION ON ITEM
 # 9A2 NOT 9A1. REVISE AS REQUIRED. SEC. R101.5.1.1.1
 FBC -ENERGY CONSERVATION.
  
 NOTE:
 WINDOW NEED LABEL SHOWING THE ENERGY U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ON THE ENERGY CALCULATIONS
 SUBMITTED. MAKE SURE THE WINDOWS MEET THIS CRITERIA
 PRIOR TO PURCHASING THEM TO AVOID CONFLICTS.
  
 2- NEW COMMENT:
 A) THE BUILDING CODE UNDER WHICH THIS PERMIT
 APPLICATION WAS SUBMITTED WAS THE 2014 FBC. CLARIFY WHY
 THE DESIGN PARAMETERS AND CODES FOR REFERENCE
 INFORMATION AND STRUCTURAL NOTE #1 WAS CHANGED ON SHEET
 A.1 TO REFERENCE THE 2017 FBC?. THERE IS NO REASON TO
 CHANGE THE REFERENCED CODE. REVISE AS REQUIRED TO
 REFERENCE THE CORRECT CODE, THE 2014 FBC AS REQUIRED BY
 CHAPTER 553 FLORIDA STATUTE.
  
 B) THE CURRENT ASCE STANDARD IS THE ASCE 7-10 NOT ASCE
 7-16. REVISE DESIGN PARAMETERS INFORMATION AND
 STRUCTURAL NOTE #2(C) AS REQUIRED BY CHAPTER 46
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  