| 2018-02-02 15:15:27 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD |
| | BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) COOLING SYSTEM AND EFFICIENCY SPECIFIED ON ITEM #12A |
| | AND 12B DON'T MATCH PLANS. THERE IS NO DUCTLESS MINI |
| | SPLIT UNIT SPECIFIED ON PLANS. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.1 FBC -ENERGY CONSERVATION. |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING BUILDER NAME, PERMITTING OFFICE. SEC. |
| | R101.5.1.1.1 FBC -ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | C) WINDOW AREA SPECIFIED ON ITEM #6(C) DOESN'T MATCH |
| | PLANS. NOTE: THERE ARE TWO WINDOWS SHOWN ON PLANS. SEE |
| | PLAN FOR SIZES AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.1 FBC -ENERGY CONSERVATION. |
| | |
| | D) REVISE ITEM #9. WALL TYPE IS MASONRY NOT WOOD FRAME. |
| | CALCULATIONS NEED TO SHOW THE R-4.1 INSULATION ON ITEM |
| | # 9A2 NOT 9A1. REVISE AS REQUIRED. SEC. R101.5.1.1.1 |
| | FBC -ENERGY CONSERVATION. |
| | |
| | NOTE: |
| | WINDOW NEED LABEL SHOWING THE ENERGY U-FACTOR AND SHGC |
| | FACTOR SPECIFIED ON THE ON THE ENERGY CALCULATIONS |
| | SUBMITTED. MAKE SURE THE WINDOWS MEET THIS CRITERIA |
| | PRIOR TO PURCHASING THEM TO AVOID CONFLICTS. |
| | |
| | 2- NEW COMMENT: |
| | A) THE BUILDING CODE UNDER WHICH THIS PERMIT |
| | APPLICATION WAS SUBMITTED WAS THE 2014 FBC. CLARIFY WHY |
| | THE DESIGN PARAMETERS AND CODES FOR REFERENCE |
| | INFORMATION AND STRUCTURAL NOTE #1 WAS CHANGED ON SHEET |
| | A.1 TO REFERENCE THE 2017 FBC?. THERE IS NO REASON TO |
| | CHANGE THE REFERENCED CODE. REVISE AS REQUIRED TO |
| | REFERENCE THE CORRECT CODE, THE 2014 FBC AS REQUIRED BY |
| | CHAPTER 553 FLORIDA STATUTE. |
| | |
| | B) THE CURRENT ASCE STANDARD IS THE ASCE 7-10 NOT ASCE |
| | 7-16. REVISE DESIGN PARAMETERS INFORMATION AND |
| | STRUCTURAL NOTE #2(C) AS REQUIRED BY CHAPTER 46 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |