Plan Review Notes
Plan Review Notes For Permit 17080429
Permit Number 17080429
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-25 06:50:14PLUMBING 1ST REVIEW**DENIED**
  
 1) WET BAR CAN NOT DISCHARGE INTO BATHROOM GROUP**
  
 912.1 HORIZONTAL WET VENT PERMITTED.ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. EACH
 WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO
 THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION