| Plan Review Notes For Permit 17080429 |
| Permit Number |
17080429 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-25 06:50:14 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) WET BAR CAN NOT DISCHARGE INTO BATHROOM GROUP** | | | | | | 912.1 HORIZONTAL WET VENT PERMITTED.ANY COMBINATION OF | | | FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME | | | FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL | | | WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR | | | THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF | | | THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE | | | DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN | | | CONNECTION TO THE HORIZONTAL BRANCH DRAIN. EACH | | | WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO | | | THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|