| Plan Review Notes For Permit 17080429 |
| Permit Number |
17080429 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-23 17:57:09 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, MECHANICAL | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- EQUIPMENT SCHEDULE ON SHEET P/M SPECIFIES "SPLIT | | | SYSTEM EQUIPMENT SCHEDULE". THERE IS NOT SPLIT SYSTEM | | | SHOWN ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2- EQUIPMENT LISTED ON THE EQUIPMENT SCHEDULE DOESN'T | | | PROVIDE HEATING. HEATING IS REQUIRED BY SEC. R303.9 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). IT DOESN'T COMPLY. | | | REVISE AS REQUIRED. | | | | | | 3- DRAWING P/M: PROVIDE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|