2017-08-23 17:57:09RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, MECHANICAL
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SCHEDULE ON SHEET P/M SPECIFIES "SPLIT
 SYSTEM EQUIPMENT SCHEDULE". THERE IS NOT SPLIT SYSTEM
 SHOWN ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- EQUIPMENT LISTED ON THE EQUIPMENT SCHEDULE DOESN'T
 PROVIDE HEATING. HEATING IS REQUIRED BY SEC. R303.9
 FBC-RESIDENTIAL, 5TH EDITION (2014). IT DOESN'T COMPLY.
 REVISE AS REQUIRED.
  
 3- DRAWING P/M: PROVIDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  