2017-08-22 16:35:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN, A
 LICENSED PROFESSIONAL. FBC 107.2.1, FS 471, 481
 2. PROVIDE REQUIRED SMOKE ALARMS. PROVIDE FLOOR PLAN OF
 THE REMAINDER OF THE HOME, SHOWING EXISTING LOCATIONS
 OF SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. FBC R314.3
 3. AFCI PROTECTION IS NOT INDICATED FOR ANY OF THE NEW
 CIRCUITS. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE
 BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL
 HAVE AFCI PROTECTION. PROVIDE CORRECTION. NEC 210.12;
 FBC RE3902.12
 4. BEDROOM DOES NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  