2017-08-09 08:03:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER USED AN EFFECTIVE WIND AREA OF 21.2
 SQUARE FEET TO DETERMINE THE COMPONENT & CLADDING ROOF
 PRESSURES. THE TRIBUTARY AREA OF THE FASTENERS FOR THE
 ROOFING MATERIAL IS LESS THAN 10 SQUARE FEET. ASCE 7-10
 USES AN EFFECTIVE AREA OF 10 SQUARE FEET WHEN A
 CLADDING FASTENER HAS A TRIBUTARY AREA OF LESS THAN 10
 SQFT. PLEASE PROVIDE CLARIFICATION AS TO WHY THE
 ENGINEER USED 21.2 SQFT AS THE EFFECTIVE WIND AREA. FBC
 107.2.1
  
 2) THE ROOFING SYSTEM (SC-127) THAT WAS SPECIFIED FROM
 THE CARLISLE SURE-WELD TPO ROOF SYSTEM PRODUCT APPROVAL
 HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS DESIGN
 PRESSURE IS NOT ADEQUATE FOR THE PERIMETER AND CORNER
 ROOF AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AT THE
 PERIMETER AND CORNER AREAS IN ACCORDANCE WITH
 LIMITATION NUMBER 5.7 ON PAGE 5 OF 6 OF THE PRODUCT
 APPROVAL (FL14083-R14). FBC 1604.2
  
 3) THE WORK DESCRIPTION ON THE PERMIT APPLICATION LISTS
 THIS PROJECT AS A RE-ROOF AND PAGE 2 OF THE ROOFING
 "FORM 110" INDICATES THAT THIS IS A RECOVER. PLEASE
 CLARIFY. FBC 107.2.1
  
 4) IF THIS IS A RECOVER, LIMITATION NUMBER 5.6 ON PAGE
 5 OF 6 OF THE PRODUCT APPROVAL (FL14083-R14), STATES
 "FOR RECOVER INSTALLATIONS, THE EXISTING ROOF SHALL BE
 EXAMINED IN ACCORDANCE WITH FBC 1510." YOU WILL ALSO BE
 REQUIRED TO HAVE THE ROOF INSPECTED BY THE CITY
 BUILDING INSPECTOR BEFORE STARTING THE RECOVER. FBC
 110.3
  
 5) ADDITIONAL INFORMATION IS REQUIRED FOR THE SKYLIGHT
 INSTALLATION. BASED ON AERIAL PHOTOGRAPHS THERE IS 16
 SKYLIGHTS THAT ARE GROUPED TOGETHER IN AN ARRAY AT THE
 CENTER OF THE ROOF. THE PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR ATTACHING TO WOOD FRAMING MEMBERS AND
 THIS ROOF HAS METAL FRAMING. PLEASE SUBMIT SIGNED AND
 SEALED ENGINEERED DRAWINGS OF THE EXISTING ROOF
 STRUCTURE WITH ALL DIMENSIONS SHOWING HOW THE SKYLIGHTS
 WILL BE ATTACHED TO THE METAL FRAME WORK. PROVIDE ANY
 CALCULATIONS AND ANY OTHER DATA NECESSARY TO SHOW THAT
 THE PROPOSED INSTALLATION WILL MEET THE WINDLOAD
 REQUIREMENTS. THE ENGINEER OF RECORD IS REQUIRED TO
 REVIEW AND APPROVE THE PRODUCT APPROVAL FOR THE
 SKYLIGHTS. FBC 107.2.1.2 & 107.2.1.3
  
  
  