Plan Review Notes
Plan Review Notes For Permit 17080296
Permit Number 17080296
Review Stop G
Sequence Number 1
Notes
Date Text
2017-08-09 03:28:541) SUBMIT A LEGIBLE COPY OF SHT.P1. ALL THE NOTES &
 DETAILS ON THIS SHEET ARE ILLEGIBLE. PLEASE DO NOT
 SUBMIT A SHEET OF THIS POOR QUALITY IN THE FUTURE AS IT
 WILL RESULT IN ANOTHER REJECTION. COMPLY WITH CITY OF
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE CAPPED RISER SHALL HAVE A SHUTOFF VALVE, THE
 REGULATOR AND A NIPPLE AND CAP TO ENSURE A SAFE SYSTEM
 FOR CONNECTION TO INTERIOR LINES.
 3) THE ENGINEERING SHEET FROM TIE DOWN ENGINEERING THAT
 BEARS A COPY OF R.F.TUCKER'S SEAL AND SIGNATURE IS NOT
 ACCEPTABLE. FLORIDA ADMINISTRATIVE CODE RULE
 61G15-23.001 READS:
 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL:
 (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS,
 OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE
 AND BEING FILED FOR PUBLIC RECORD;
 A COPY OF A SIGNED AND SEALED DOCUMENT IS IN VIOLATION
 OF THE ABOVE NOTED RULE. THEREFORE, IF THIS SHEET IS
 GOING TO BE SUBMITTED BEARING R.F.TUCKER'S SEAL AND
 SIGNATURE, IT MUST BEAR AN ORIGINAL SEAL AND SIGNATURE
 PER THE RULE. THE CODE DOES NOT REQUIRE SIGNED AND
 SEALED ENGINEERING FOR THE ANCHORING OF THE TANK.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  