2017-10-17 13:09:291ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A201 DETAIL #4 SHOWS A 4X5 DOWN SPOUT THE
 CALCULATIONS ON SHT M-1.0 DOES NOT MATCH PLEASE LABEL
 EACH DOWN SPOUT WITH THE SQFT DRAINED BY EACH ONE IT
 SHALL COMPLY WITH FBC PL TABLE 1106.2(2)
  
 2. PLEASE PROVIDE CALCULATIONS FOR THE GUTTER SHALL
 COMPLY WITH FBC PL TABLE 1106.6
  
 3. SHT. M-2.2 GENERAL NOTE #2 THE MIXING VALVE SHALL BE
 A WATER-TEMPERATURE LIMITING DEVICE COMPILING WITH ASSE
 1070 OR CSA B125.3 PER FBC PL 416.5
  
 4. SHT. A501 DETAIL #20 PLEASE LABEL THE CLEAR FLOOR
 SPACE WITH THE DIMENSIONS PER FBC ACC 604.3.1 AND 305
  
 5. PROVIDE A SANITARY AND WATER ISOMETRIC DRAWING. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  