| Plan Review Notes For Permit 17080289 |
| Permit Number |
17080289 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-10-17 13:09:29 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT A201 DETAIL #4 SHOWS A 4X5 DOWN SPOUT THE | | | CALCULATIONS ON SHT M-1.0 DOES NOT MATCH PLEASE LABEL | | | EACH DOWN SPOUT WITH THE SQFT DRAINED BY EACH ONE IT | | | SHALL COMPLY WITH FBC PL TABLE 1106.2(2) | | | | | | 2. PLEASE PROVIDE CALCULATIONS FOR THE GUTTER SHALL | | | COMPLY WITH FBC PL TABLE 1106.6 | | | | | | 3. SHT. M-2.2 GENERAL NOTE #2 THE MIXING VALVE SHALL BE | | | A WATER-TEMPERATURE LIMITING DEVICE COMPILING WITH ASSE | | | 1070 OR CSA B125.3 PER FBC PL 416.5 | | | | | | 4. SHT. A501 DETAIL #20 PLEASE LABEL THE CLEAR FLOOR | | | SPACE WITH THE DIMENSIONS PER FBC ACC 604.3.1 AND 305 | | | | | | 5. PROVIDE A SANITARY AND WATER ISOMETRIC DRAWING. PER | | | WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|