| Plan Review Notes For Permit 17080289 |
| Permit Number |
17080289 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-04 09:37:25 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | A SEPARATE ROOF PERMIT IS REQUIRED. SUBMIT THE PRODUCT | | | APPROVAL, REVIEWED BY DESIGNER OF RECORD, WITH ROOF | | | PERMIT APPLICATION AND ENGINEERING (IF REQUIRED). | | | | | | ROOF COVERING IS TO MEET THE DESIGN PRESSURES SPECIFIED | | | ON PAGE 2 (BUTLER): | | | ZONE 1 -43.31 | | | ZONE 2 -72.68 | | | ZONE 3 -109.38 | | | | | | |
|