2017-09-13 11:10:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080289
 9/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.1: DETAIL 1/M-6.2 DOES NOT EXIST. THERE IS
 NO M-6.2 PLAN SHEET IN THE SETS OR IN THE INDEXES.
  
 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ROOF FANS- SECTION 301.15.
  
 3) SUBMIT PRODUCT APPROVALS OR NOA'S FOR THE NEW AND
 RELOCATED LOUVERS- 9N-B FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER