| Plan Review Notes For Permit 17080289 |
| Permit Number |
17080289 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-13 11:10:07 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080289 | | | 9/13/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-2.1: DETAIL 1/M-6.2 DOES NOT EXIST. THERE IS | | | NO M-6.2 PLAN SHEET IN THE SETS OR IN THE INDEXES. | | | | | | 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE ROOF FANS- SECTION 301.15. | | | | | | 3) SUBMIT PRODUCT APPROVALS OR NOA'S FOR THE NEW AND | | | RELOCATED LOUVERS- 9N-B FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|