2017-09-07 15:40:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080284
 9/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M1.2: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF AHU-10- SEE SECTION 606.2.1.
  
 2) M6.1: REFER TO TABLE 7-1 ASHRAE 170-2008 AND
 INDICATE REQUIRED DESIGN PARAMETERS AND PRESSURE
 RELATIONSHIPS FOR THE IR LAB AND ADJACENT ROOMS AS
 OUTLINED IN THE TABLE. PLEASE NOTE THAT THE MAJORITY OF
 THE LABS LISTED IN THE TABLE REQUIRE NEGATIVE PRESSURE
 AND EXHAUST SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER