| Notes |
| Date |
Text |
| 2017-09-07 15:40:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080284 | | | 9/7/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M1.2: A DUCT SMOKE DETECTOR IS REQUIRED IN THE | | | RETURN AIR SYSTEM OF AHU-10- SEE SECTION 606.2.1. | | | | | | 2) M6.1: REFER TO TABLE 7-1 ASHRAE 170-2008 AND | | | INDICATE REQUIRED DESIGN PARAMETERS AND PRESSURE | | | RELATIONSHIPS FOR THE IR LAB AND ADJACENT ROOMS AS | | | OUTLINED IN THE TABLE. PLEASE NOTE THAT THE MAJORITY OF | | | THE LABS LISTED IN THE TABLE REQUIRE NEGATIVE PRESSURE | | | AND EXHAUST SYSTEMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|