| 2018-06-05 17:36:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #17080211 |
| | 6/5/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW VRF SYSTEM- SECTION C403.2.1 FBC EC. |
| | |
| | 2) SHEET M-1: REFER TO SECTION 501.4 FBC M AND INDICATE |
| | HOW COMPLIANCE WILL BE MET FOR PRESSURE EQUALIZATION. |
| | WILL THE EXHAUST BE LINKED TO THE OUTDOOR AIR SYSTEM? |
| | THE PLANS APPEAR TO INDICATE A MANUAL SWITCH FOR THE |
| | FAN. PLEASE PROVIDE AN AIR BALANCE CALCULATION. |
| | |
| | 3) M-1: SHEET PROVIDE AN ACCESS PANEL FOR THE INLINE |
| | FAN- SECTION 306.1 FBC M. |
| | |
| | 4) M-1: EXHAUST VENTILATION IS REQUIRED FOR THE SHOWER |
| | ROOM- TABLE 403.3.1 |
| | |
| | 5) M-1: PROVIDE WINDLOAD ENGINEERING FOR INSTALLATION |
| | OF THE CONDENSER AND CONDENSER STAND- SECTION 301.15 |
| | FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |