| Plan Review Notes For Permit 17080211 |
| Permit Number |
17080211 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-16 10:28:07 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #17080211 | | | 8/16/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE HAIR SALON REQUIRES EXHAUST VENTILATION AT A | | | RATE OF 0.60 CFMS PER SQ. FT., AND THE RECIRCULATION OF | | | ANY AIR FROM THE SPACE IS PROHIBITED- SEE TABLE 403.3 | | | AND FOOTNOTE B. PLEASE PROVIDE A SYSTEM THAT MEETS | | | COMPLIANCE. | | | | | | 2) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 3) PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE PLAN | | | WITH CORRESPONDING DRAWINGS AND DETAILS. SHOW ALL | | | ALTERATIONS TO THE EXISTING HVAC SYSTEMS. | | | | | | 4) THE BUILDING PLANS EXAMINER IS REQUIRING CODE | | | COMPLIANT PLANS DONE BY A LICENSED ARCHITECT WHICH WILL | | | CLARIFY WHETHER THE PROPOSED PROJECT IS A CHANGE OF | | | OCCUPANCY OR CHANGE OF USE FROM THE PREVIOUS OCCUPANCY. | | | BASED ON THOSE COMMENTS, THE MECHANICAL REVIEW IS | | | STOPPED AT THIS TIME UNTIL NEW PLANS ARE RESUBMITTED | | | FOR REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|