| 2017-08-22 13:18:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SMOKE ALARM IS MISSING IN MASTER BEDROOM AND THE |
| | AREA ADJACENT TO THE MASTER BEDROOM, PROVIDE |
| | CORRECITON. FBC RE314.3 |
| | 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH |
| | GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC |
| | 210.70(A)(2)(B), FBC RE3903.3 |
| | 3. FOR THE AHU, A LUMINAIRE CONTROLLED BY A SWITCH |
| | LOCATED AT THE REQUIRED PASSAGEWAY OPENING AND A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT OR NEAR THE |
| | APPLIANCE LOCATION. FBC RE M1305.1.3.1 |
| | 4. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE |
| | CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER |
| | CODE. PROVIDE CORRECTION. NEC 210.11(C)(1), |
| | 210.52(B)(2); FBC RE3703.2 |
| | 5. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 |
| | 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| | 107.2.1 |
| | 7. PROVIDE CORRECTION FOR AFCI NOTE. NOTE CURRENTLY |
| | STATES THAT ALL "RECEPTACLES ..... SHALL HAVE AFCI |
| | PROTECTION." CODE STATES: "ALL 120-VOLT, SINGLE PHASE, |
| | 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION". NEC 210.12; FBC |
| | RE3902.12 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |