| 2018-08-27 15:13:31 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | |
| | NEW COMMENT.: |
| | |
| | 5. THIS PLAN HAS TWO DIFFERENT ADDRESSES AND TWO PERMIT |
| | APPLICATIONS IN THE PACKET. IT IS NOT POSSIBLE TO ISSUE |
| | PART OF A PACKET. IT IS RECOMMENDED THAT THE PLANS BE |
| | SEPARATED FOR EACH LOCATION AND SUBMITTED AS TWO |
| | SEPARATE PACKETS WITH THE APPROPRIATE PERMIT |
| | APPLICATION. THIS PLAN REVIEW WILL REMAIN IN FAILED |
| | STATUS UNTIL SUCH TIME THAT THE COMMENTS FOR 18070142 |
| | ARE ADDRESSED SATISFACTORILY, OR THE PERMITS ARE |
| | SEPARATED. WPB FBC 105.1, 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |