| 2017-08-16 10:15:14 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE AIC RATING OF THE SERVICE |
| | EQUIPMENT, ATS, AND LIFT STATION CONTROL PANEL IS |
| | ADEQUATE. NEC 110.9, 110.10, 409.110(4) |
| | 2. PROVIDE AIC RATING OF SERVICE DISCONNECT, ATS, AND |
| | LIFT STATION CONTROL PANEL. NEC 110.3, 110.9, |
| | 409.110(4) |
| | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 4. PLAN SHOWS A 60KW GENERATOR, WHICH HAS A CAPACITY OF |
| | APPROXIMATELY 72 AMPS AT 480 VOLT. THE DEMAND LOAD |
| | SUPPLIED STATES THE LOAD IS 97.75 AMPS, WHICH EXCEEDS |
| | THE CAPACITY OF THE GENERATOR. PROVIDE CORRECTION. NEC |
| | 702.4 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |